11KV/33KV S13-M-RL series oil-immersed three-dimensional wound core distribution transformer

     

    Model meaning

    Performance Parameters

    S13-M series 10kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 6 6.3 6.6 10 10.5 11 ±2x2.5 ±5 0.4 Dyn11 Yzn11 Yyno 80 630/600 1.2 4
    50 100 910/870 1
    63 110 1090/1040 0.95
    80 130 1310/1250 0.95
    100 150 1580/1500 0.9
    125 170 1890/1800 0.9
    160 200 2310/2200 0.8
    200 240 2730/2600 0.8
    250 290 3200/3050 0.7
    315 340 3830/3650 0.7
    400 410 4520/4300 0.65
    500 480 5410/5150 0.65
    630 Dyn11 Yyno 570 6200 0.45 4.5
    800 700 7500 0.45
    1000 830 10300 0.45
    1250 970 12000 0.4
    1600 1170 14500 0.4
    2000 1550 18300 0.3 5
    2500 1830 21200 0.3
    Note: For transformers with a rated capacity of 500kVA and below, the load loss value above the slash in the table applies to Dyn11 or Yzn11 junction groups, and the load loss value below the slash applies to Yyno junction groups.

    S13-M series 20kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 20 22 24 ±2x2.5 ±5 0.4 Dyn11 Yzn11 Yyno 80 690/660 2.1 5.5
    50 100 1010/960 2
    63 110 1200/1150 1.9
    80 130 1440/1370 1.8
    100 150 1730/1650 1.6
    125 170 2080/1980 1.5
    160 200 2540/2420 1.4
    200 240 3000/2860 1.3
    250 290 3520/3350 1.2
    315 340 4210/4010 1.1
    400 410 4970/4730 1
    500 480 5940/5660 1
    630 570 6820 0.9 6
    800 700 8250 0.8
    1000 830 11330 0.7
    1250 970 13200 0.7
    1600 1170 15950 0.6
    2000 1550 19140 0.6
    2500 1830 22220 0.5

    S13-M series 35kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    50 35 38.5 ±2x2.5 ±5 0.4 Dyn11 Yyno 130 1200/1140 1.05 6.5
    100 185 2010/1910 0.9
    125 215 2370/2260 0.9
    160 225 2820/2680 0.8
    200 270 3320/3160 0.8
    250 320 3950/3760 0.75
    315 380 4750/4530 0.75
    400 460 5740/5470 0.65
    500 540 6910/6580 0.65
    630 660 7860 0.5
    800 780 9400 0.5
    1000 920 11500 0.5
    1250 1120 13900 0.45
    1600 1350 16600 0.45
    2000 1590 19700 0.4
    2500 1890 23200 0.4
    Note: For transformers with a rated capacity of 500kVA and below, the load loss value above the slash in the table applies to the Dyn11 or Yzn11 connection group, and the load loss value below the slash applies to the Yyno connection group.