SCBH15 series amorphous alloy dry-type transformer
Overview
The no-load loss of the amorphous alloy dry-type transformer is 75% lower than that of Group 1 in Table 4 of GB/T10228, and the load loss is 15% lower than that of Table 4 of GB/T10228. It is the most advanced energy-saving dry-type transformer in the world.
Model Specification
Usage environment
Ambient temperature: -51℃+40℃
The average temperature of the hottest month is +30℃
The hottest annual average temperature is +20℃
The altitude does not exceed 1000m
The waveform of the power supply voltage is approximately a sine wave
The three-phase power supply voltage should be roughly symmetrical
There is no obvious pollution in the installation environment
Indoor use
Product Standards
GB/T22072-2008 GB1094.11-2007
Rated high voltage: 10 (10.5, 11, 6, 6.3, 6.6) kV
Rated low voltage: 0.4kV
Tap range: non-excitation voltage regulation (±5%, ±2x2.5%)
On-load voltage regulation: (±4x2.5%)
Connection group: Dyn11 or YynO
Insulation level: LI75AC35/AC5
Product Usage
This product has the advantages of low no-load loss, oil-free, flame-retardant and self-extinguishing, moisture-resistant, crack-resistant and maintenance-free. Any place where ordinary dry transformers are currently used can be replaced by amorphous dry transformers, which can be used in high-rise buildings, commercial centers, subways, airports, stations, industrial and mining enterprises and power plants. It is especially suitable for installation and use in places with high fire protection requirements such as flammable and explosive.