Leave Your Message

SG(ZB)10 series non-encapsulated coil dry-type transformer

 

    Product Description

    Product Standards
    GB/T10228-2015 GB1094.11-2007
    Rated high voltage: 10 (10.5, 11, 6, 6.3, 6.6) kV
    Rated low voltage: 0.4kV
    Tap range: non-excitation voltage regulation (±5%, ±2x2.5%)
    On-load voltage regulation: (±4x2.5%)
    Connection group: Dyn11 or Yyn0
    Insulation level: LI75AC35/AC5
    Note: When the maximum ambient temperature is >40°C and the altitude is >1000m, corrections should be made according to the relevant provisions of the national standard. Ask the user to put it forward when ordering.

    Model specification

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss 75℃(W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    100 6 6.3 6.6 10 10.5 11 ±2x2.5 ±5 0.4 Dyn11 Yyn0 400 1370 1.5 4
    125 470 1620 1.3
    160 540 1870 1.3
    200 620 2220 1.1
    250 720 2420 1.1
    315 880 3050 1
    400 980 3500 1
    500 1160 4290 1
    630 1300 5240 0.85 6
    800 1520 6110 0.85
    1000 1770 7140 0.85
    1250 2090 8510 0.85
    1600 2450 10290 0.85
    2000 3050 12690 0.7
    2500 3600 15080 0.7
    1600 2450 11370 0.85 8
    2000 3050 14020 0.7
    2500 3600 16590 0.7
    Note: On-load voltage regulating series transformers only adjust the following two data: 1. The weight increases by 100kg; 2. The on-load switch is arranged on the side a of the transformer and increases by 650mm or the front b increases by 750mm.