    Product description

    Transformers can convert the grid voltage into the voltage required by the system or load to realize the transmission and distribution of electric energy. This transformer can replace the silicon steel core transformer and is widely used in outdoor power distribution systems. The large-scale operation of this product into the network can achieve good energy-saving effects and reduce atmospheric pollution. This product is particularly suitable for areas with insufficient power and large load fluctuations, as well as areas where routine maintenance is difficult. Since the transformer adopts a fully sealed structure, the insulating oil and insulating medium are not polluted by the atmosphere, so it can operate in humid environments and is an ideal power distribution equipment in the vast power distribution network in cities and rural areas.

    Features
    An energy-saving product, the no-load loss is about 75% lower than that of the S9 transformer; it has low loss, less heat, low temperature rise, and stable operation; it has an advanced and reasonable structure and strong short-circuit resistance; it has strong overload capacity, is safe and reliable, has strong corrosion resistance, and is free of charge. maintain.

    Model meaning

    Product Standards

    GB1094.1~2-2013 G B/T 25446-2010

    Rated high voltage: 10 (10.5, 11, 6, 6.3, 6.6) kV

    Rated low voltage: 0.4kV

    Tap range: non-excitation voltage regulation (±5%, ±2x2.5%)

    Connection group: Dyn11 or Yyno

    Insulation level: LI75AC35/AC5

    S(B)H15-M series 10kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 6 6.3 10 10.5 11 ±2x2.5 ±5 0.4 Dyn11 Yyno 33 630/660 1.5 4
    50 43 910/870 1.2
    63 50 1090/1040 1.1
    80 60 1310/1250 1
    100 75 1580/1500 0.9
    125 85 1890/1800 0.8
    160 100 2310/2200 0.6
    200 120 2730/2600 0.6
    250 140 3200/3050 0.6
    315 170 3830/3650 0.5
    400 200 4520/4300 0.5
    500 240 5410/5150 0.5
    630 320 6200 0.3 4.5
    800 380 7500 0.3
    1000 450 10300 0.3
    1250 530 12000 0.2
    1600 630 14500 0.2
    2000 750 18300 0.2 5
    2500 900 21200 0.2
    Note: For transformers with a rated capacity of 500kVA and below, the load loss value above the slash in the table applies to the Dyn11 or Yzn11 connection group, and the load loss value below the slash applies to the Yyno connection group.