S11 series oil-immersed transformer

    GB1094.1~2-2013 GB/T 6451-2015
     Rated high voltage: 10 (10.5, 11, 6, 6.3, 6.6) kV
     Rated low voltage: 0.4kV
     Tap range: non-excitation voltage regulation (±5%, ±2x2.5%)
     On-load voltage regulation: (±4x2.5%)
     Connection group: Dyn11 or Yyn0
     Insulation level: LI75AC35/AC5

    Model Meaning

    S11-M series 10kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 6 6.3 6.6 10 10.5 11 ±2x2.5 ±5 0.4 Dyn11 Yzn11 Yyn0 100 630/600 1.5 4
    50 130 910/870 1.3
    63 150 1090/1040 1.2
    80 180 1310/1250 1.2
    100 200 1580/1500 1.1
    125 240 1890/1800 1.1
    160 280 2310/2200 1
    200 340 2730/2600 1
    250 400 3200/3050 0.9
    315 480 3830/3650 0.9
    400 570 4520/4300 0.8
    500 680 5410/5150 0.8
    630 Dyn11 Yyn0 810 6200 0.6 4.5
    800 980 7500 0.6
    1000 1150 10300 0.6
    1250 1360 12000 0.5
    1600 1640 14500 0.5
    2000 1940 18300 0.4 5
    2500 2290 21200 0.4
    Note 1: For transformers with a rated capacity of 500kVA and below, the load loss value above the diagonal line in the table applies to the Dyn11 or Yzn11 connection group, and the load loss value below the diagonal line applies to the Yyno connection group. Note 2: For transformers with rated capacity of 500kVA and below, the load loss value above the diagonal line in the table applies to the Dyn11 connection group, and the load loss value below the diagonal line applies to the Yyn0 connection group.

    S11-M series 20kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 20 22 24 ±5% ±2x2.5% 0.4 Dyn11 Yzn11 Yyn0 100 690/660 2.1 5.5
    50 130 1010/960 2
    63 150 1200/1150 1.9
    80 180 1440/1370 1.8
    100 200 1730/1650 1.6
    125 240 2080/1980 1.5
    160 280 2540/2420 1.4
    200 340 3000/2860 1.3
    250 400 3520/3350 1.2
    315 480 4210/4010 1.1
    400 570 4970/4730 1
    500 680 5940/5660 1
    630 810 6820 0.9 6
    800 980 8250 0.8
    1000 1150 11330 0.7
    1250 1380 13200 0.7
    1600 1650 15950 0.6
    2000 1950 19140 0.6
    2500 2340 22220 0.5

    S11 series 35kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    50 35 38 ±5% ±2x2.5% 0.4 Dyn11 Yyn0 160 1200/1140 1.3 6.5
    100 230 2010/1910 1.1
    125 270 2370/2260 1.1
    160 280 2820/2680 1
    200 340 3320/3160 1
    250 400 3950/3760 0.95
    315 480 4750/4530 0.95
    400 580 5740/5470 0.85
    500 680 6910/6580 0.85
    630 830 7860 0.65
    800 980 9400 0.65
    1000 1150 11500 0.65
    1250 1400 13900 0.6
    1600 1690 16600 0.6
    2000 1990 19700 0.55
    2500 2360 23200 0.55
    Note 1: For transformers with rated capacity of 500kVA and below, the load loss value above the slash in the table applies to the Dyn11 connection group, and the load loss value below the slash applies to the Yyn0 connection group

    S11 series 35kV three-phase double winding non-excitation voltage regulating power transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    630 35 ±2x2.5% ±5% 3.15 6.3 10.5 Yd11 830 7860 0.65 6.5
    800 980 9400 0.65
    1000 1150 11500 0.65
    1250 1400 13900 0.55
    1600 1690 16600 0.45
    2000 2170 18300 0.45
    2500 2560 19600 0.45
    3150 35-38.5 ±2x2.5% ±5% 3.15 6.3 10.5 3040 23000 0.45 7
    4000 3610 27300 0.45
    5000 4320 31300 0.45
    6300 5240 35000 0.45
    8000 35-38.5 ±2x2.5% 3.15 3.3 6.3 6.6 10.5 YNd11 7200 38400 0.35 8
    10000 8700 45300 0.35
    12500 10000 53800 0.3
    16000 12100 65800 0.3
    20000 14400 79500 0.3
    25000 17000 94000 0.25 10
    31500 20200 112000 0.25
    Note: For transformers with a low voltage of 10.5kVA, products with the connection group number DYn11 can be provided. For transformers with a rated capacity of 3150kvA and above, the -5% tap position is the maximum current tap.

    SZ11 series 35kV three-phase double winding on-load voltage regulating power transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    2000 35 ±3x2.5% 6.3 10.5 Yd11 2300 19200 0.5 6.5
    2500 2720 20600 0.5
    3150 35-38.5 3230 24700 0.5 7
    4000 3870 29100 0.5
    5000 4640 34200 0.5
    6300 5630 36700 0.5 8
    8000 YNd11 7870 40600 0.4
    10000 9280 48000 0.4
    12500 6.3 6.6 10.5 10900 56800 0.35
    16000 13100 70300 0.35
    20000 15500 82700 0.3
    25000 18300 97800 0.3 10
    31500 21800 116000 0.3
    Note: For low-voltage transformers with a voltage of 10.5kVA, products with the connection group number DYn11 are available. -7.5% tap position is maximum current tap.

    S11-M series 20kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    30 20 22 24 ±5% ±2x2.5% 0.4 Dyn11 Yzn11 Yyno 100 690/660 2.1 5.5
    50 130 1010/960 2
    63 150 1200/1150 1.9
    80 180 1440/1370 1.8
    100 200 1730/1650 1.6
    125 240 2080/1980 1.5
    160 280 2540/2420 1.4
    200 340 3000/2860 1.3
    250 400 3520/3350 1.2
    315 480 4210/4010 1.1
    400 570 4970/4730 1
    500 680 5940/5660 1
    630 810 6820 0.9 6
    800 980 8250 0.8
    1000 1150 11330 0.7
    1250 1380 13200 0.7
    1600 1650 15950 0.6
    2000 1950 19140 0.6
    2500 2340 22220 0.5

    S11 series 35kV three-phase two-winding non-excitation voltage regulating distribution transformer

    Rated capacity (kVA) Voltage combination and tap range association group label No-load loss (W) Load loss (W) No-load current(%) Short circuit impedance(%)
    High voltage (kV) High voltage tap range (%) Low voltage (kV)
    50 35 38.5 ±5% ±2x2.5% 0.4 Dyn11 Yyno 160 1200/1140 1.3 6.5
    100 230 2010/1910 1.1
    125 270 2370/2260 1.1
    160 280 2820/2680 1
    200 340 3320/3160 1
    250 400 3950/3760 0.95
    315 480 4750/4530 0.95
    400 580 5740/5470 0.85
    500 680 6910/6580 0.85
    630 830 7860 0.65
    800 980 9400 0.65
    1000 1150 11500 0.65
    1250 1400 13900 0.6
    1600 1690 16600 0.6
    2000 1990 19700 0.55
    2500 2360 23200 0.55